Gas could be the most expensive, least reliable path to grid stability

kwinana-power-station

The discussion on inertia and synchronous generation is rather confused. Inertia is necessary because it provides stability to the grid. “Strength” and “stiffness” are terms that are used to show that lots of rotating inertia is “good’ or even essential to a stable grid. Because it was free it is often assumed that the system needs as much generator inertia as it always had.

But inertia is just one way to supply stability and it can be argued that beyond more than a certain minimum level, generator inertia is an expensive and anachronistic way of providing stability.

Stability is required to protect timing circuits, minimise mechanical loads on motors and generators caused by changing speed, prevent overheating of inductive loads like AC motors and most of all to prevent voltage/frequency oscillations after fast changes in load or generation e.g. from a loss of a connection or generator or even start-up of all the hot water services at 10PM.

Inertia is one simple way of providing stability because the rotating mass of the generators absorbs or disburses energy by small changes in speed.

While the inertia of turbines is large, it is only useful as a store of energy if you can use it.  Most of the energy stored in a rotating turbo-generator is unavailable because the energy is 1/2Jω2 where ω is the angular velocity and J the rotary inertia. As the angular velocity is only supposed to vary by 0.15Hz in 50Hz you can only use 0.6% (49.85/50)2 of the inertia in the system to stabilise the load. Even if a 1Hz short term deviation is allowed it is still only 4% of the system inertia.

The key to stability is not so much the inertia itself but the synchronous nature of an AC system which locks all the turbines and loads together at the same frequency, thus inertia is not just that of one generator but all the synchronous generators, the capacitance of the transmission and distribution network and even all the AC motors and loads on the load side. These later contributors are still there, even if some of the generation is no longer synchronous.

The downside of inertia is that once it is given up it must be replaced. So, if system frequency falls by 1Hz, to recover the frequency a large fraction of the output response from the remaining generators is used just to spin all the generators and loads back up to speed rather than just supply lost power to the grid. In the best case, it will prolong the frequency disturbance. In worst case the extended frequency deviation will trigger protection circuits and more widespread faults.

In a conventional system inertia provides the first 0.1-10 seconds of load disturbance response and it was free. A steam plant is quite good for the next 3-6 seconds after a disturbance because there is a quantity of steam in the steam chest which can be released quickly.

If the lost generation stays off line steam is then limited because it has slow ramping after that first steam dump. Hydro comes up after 20-150 seconds but has excellent stability and very fast ramps. The combination of inertia of water in the penstock and rotary inertia of the generator gives very stable ramping and for large scale power changes, hydro seems to offer the best combination of ramp rate and stability.

Gas turbines respond quite well after 8-30 seconds, then ramp quickly if they don’t stall or oscillate which they are prone to do at low loads. It is clear that “the straw that broke the camel’s back” in the SA blackout was the failure of gas turbine generators at the Quarantine station to respond properly to rapidly increasing demand.

However, even if inertia is seen as desirable at the plant level, gas turbine plants have no more inertia per MW than wind and many of them are operated slaved to the largest generator(s) because it is simpler and more efficient.

But if the key large generator(s) are for some reason isolated from the grid, the gas turbines will sag under the increased load and they will have limited mechanism or perhaps, if they are already at full load, even capacity, to respond. So, within fractions of a second their frequency will start to fall just as quickly as a group of wind turbines.

Even if governor response is fast, maximum stable ramp rates are around 5-10% per minute usually starting at less than that (they tend to have S shaped response curves) Gas turbines have another weakness which means that their inertia is of less value to the grid.

If frequency falls the compressors slow down reducing compression ratio and thus power so even more so more of the governor response is needed just to compensate for reduced air flow.

Finally, gas turbines are relatively low inertia probably about 1/3rd of an equivalent steam generator. Typically, the rotating inertia constant is around 3 which means that the total rotary inertia is around 3 seconds of maximum generation capacity.

Given that only 4% maximum is available as inertia services it means that a 250MW generator can compensate for about 3*250*.04 MW seconds or 30MW for 1 second or 6MW for 5 seconds. A 10MW battery system can provide 10MW for 40-200 minutes

In summary, a gas turbine based system (without spare backup in the form of interconnectors or hydro), which loses 30% of generation quickly will crash just as surely as SA did. In fact there is a good argument to suggest that a system with a large proportion of gas turbines is possibly more vulnerable to short term instability than a modern renewable based system with storage.

Wind plants are also run in slave mode because they were originally minor contributors to the system and had to follow the big generators.  However modern wind plants can operate in a synchronous fashion; it is a matter of supplying them with advanced power converters which have that capacity, as can smart inverters in solar plants.

They can in millisecond time frames adjust power output to keep frequency and voltage constant. Of course, if there is not enough power, the system will crash just as it will if you overload a gas turbine or a coal plant.

However, a key advantage of modern wind (and hydro) turbines is that they can be variable speed machines so they can give up perhaps 10% of their mechanical rotational energy while still maintaining electrical frequency. As we have seen synchronous gas or steam turbine can only give up 0.6-4% of its rotational energy before frequency falls well outside the allowable band.

Figure 1 old high inertia Diesel vs new low inertia 230kg reduced to 53kg but the new unit has much better speed stability under changing loads
Figure 1 old high inertia Diesel vs new low inertia 230kg reduced to 53kg but the new unit has much better speed stability under changing loads

Then there is the question of how much inertia is needed anyway. In the past, it was free so the more the better.

Just as early steam engines had large flywheels because their response to load changes was poor, many other systems from power grids to diesel engines, machine tools and even aircraft engines used inertia to compensate for the inadequacies of the control systems.

Modern fast response controls mean that in all these applications inertias have been reduced because a) inertia costs money and b) while it does damp unwanted disturbance, it also slows response to real load changes, so modern machinery is faster and more accurate because inertia has been reduced. With proper engineering the same can apply to a power system.

The alternative to conventional “spinning reserves” (i.e. turbines running just in case) is storage. Batteries, flywheels, pumped hydro storage and power to heat.

All these have far better ramp rates than gas turbines, have fixed costs not subject to wide fluctuations in fuel price and because of their rapid response rates, provide a much better bridge to hold up voltage and frequency while larger generators build up power. Of course, gas or steam turbines are much better to cover long outages because they can run for days, weeks or months if necessary.

Therefore, a modern system with batteries, smart inverters and synthetic inertia on wind turbines and solar plants can reach full power in about 50-100ms so inertia only needs to cover the period from t0 (the time where the incident occurs) to t0+ 50-150msec.

In a conventional, mainly gas turbine system like SA, if it was without interconnects, inertia needs to cover most of the response for at least 10 seconds and up to 100 so the system needs 50-200 times as much inertia as in a fully battery supported system. This observation has been verified by a successful trial in Ireland where a 10MW battery is providing equivalent short term response to a 100MW gas turbine.

Batteries can also be supplemented by supercapacitors, rotary condensors spinning at synchronous speed, or asynchronous flywheels which can supply 20-100 times the power to inertia ratio that a spinning generator can, so it is clear that in a modern grid the amount of generator inertia required is orders of magnitude less than that assumed when the current grid was built.

This is not to stay longer term support/backup of renewables is not required, it is simply that grid stability can be provided at far less cost than from additional synchronous generators. The point is not to eliminate power supply from gas, it is to give gas generators time to ramp up safely so the generators are more efficient and fuel is not wasted on spinning reserves.

This is why most of the recently contracted battery storage systems in the UK have been located at gas and biofuel power stations. It means the power stations can sell more power at peak demand and turn off altogether at times of low demand saving fuel and wear and tear because they don’t need to run at very low loads “just in case”. They can also arbitrage excess renewables, coal or nuclear when prices are low to recharge their batteries and resell the power at double or triple the price hours or days later.

In conclusion, probably the most expensive, least reliable way to supply grid stability is by adding gas turbines, if the primary purpose is to add inertia. Inertia is not the goal, frequency and voltage stability is. Arguing for more inertia is a bit like saying heavy cars are safer than small cars in some accidents so all cars should be as heavy as possible.

Comments

15 responses to “Gas could be the most expensive, least reliable path to grid stability”

  1. John P Avatar
    John P

    As some readers of this site will know, I have been living ‘off grid’ for the last 25 years. I have a top quality inverter sitting on suitably large battery and as long as the battery is in a good state of charge, the inverter will do everything required. It comes with synthetic inertia electronically built in. So I make a point of ensuring that the battery is always in a good state of charge. This means that the systems (two different installations sequentially) have never failed or even “browned out”. And I certainly don’t want any rotating shaft in the system.

    1. Alastair Leith Avatar
      Alastair Leith

      Hows the frequency stability? does it follow the grid frequency when it wanders to to it’s nadair and back?

      1. Ian Porter Avatar
        Ian Porter

        Frequency stability in an off-grid/islanded system is not so important actually. About the worst thing that happens if you are a ‘little off’ is the clocks are off! The reason for grid-wise integrity is due to the nature of ‘load following’ which of course is inherently associated with grid-wide frequency. (NOTE: Of course it does’nt followthe grid frequency since it’s islanded – unless the owner decides he wants to be locked into grid frequency for synchronising reasons – like if he has an interconnect circuit)

        1. Alastair Leith Avatar
          Alastair Leith

          Oh thanks Ian, i didn’t pick up it was off grid! was thinking about your comment the other day of potentially millions of inverters hunting for frequency if measures not put in place, actually.

  2. Gnällgubben Avatar
    Gnällgubben

    Great article explaining inertia and comparing alternatives!

  3. Peter G Avatar
    Peter G

    Thanks for the excellent article Peter, especially “start-up of all the hot water services at 10PM” a truly amazing madness in 2017!

    I was inquisitive regarding what, if any, particularities for frequency control you think may arise in SA’s due to importing ‘unresponsive’ frequency from the larger NEM via the Heywood AC link.

    Giles reported in an earlier article that AEMO said that SA fell out of sync with the NEM prior to the system black last year.

    1. Ellendcallanan Avatar
      Ellendcallanan

      If you were looking for a way to earn some extra income every week… Look no more!!!! Here is a great opportunity for everyone to make $95/per hour by working in your free time on your computer from home… I’ve been doing this for 6 months now and last month i’ve earned my first five-figure paycheck ever!!!! Learn more about it on following link
      TopJobsWorldNetworkGroupSoft/Media/Net……

    2. Farmer Dave Avatar
      Farmer Dave

      Great article! It was good to have the physics of how turbine generators provide short term frequency stability explained so well. The fundamentals of gas turbines providing such short term frequency stability are so poor, that their good press in this area speaks to me of successful lobbying by vested interests.

  4. Alen T Avatar
    Alen T

    Thanks for the article. I would strongly suggest hope have made a submission to the Finkel review.

  5. Alastair Leith Avatar
    Alastair Leith

    “Gas turbines respond quite well after 8-30 seconds, then ramp quickly if they don’t stall or oscillate which they are prone to do at low loads. It is clear that “the straw that broke the camel’s back” in the SA blackout was the failure of gas turbine generators at the Quarantine station to respond properly to rapidly increasing demand.”

    Somebody might want to tell Senator Backs who, at the Perth leg of the Coal Closure Senate Enquiry decided to answer his own question and selectively “repeat” prior testimony that at fault in SA was 1. Wind Generators failing 2. wind, 3. wind etc etc

    1. Ian Porter Avatar
      Ian Porter

      This is due to the ‘spooling rate’: the time required to overcome the required compression lag (like turbo lag in automotive applications). In industrial and AE gas turbines there are solutions avaiable to overcome this – compressed air storage – you don’t need much either, so not terribly costly.

  6. Alastair Leith Avatar
    Alastair Leith

    This study (power modelling) by GE in 2012 of the largest grid in the US, the Western Interconnected showed that fourth gen wind turbines with frequency control technology fitted makes for a much more resilient grid than (largely fossil) existing grid.

    http://www.cigre.org/content/download/16939/680271/version/1/file/C4_113_2012.pdf

    Also this helpful power point presentation by Miller.

    And this paper argues Gen IV turbines fitted with FR can be one of the most cost effective way of providing primary frequency response.
    https://digital.library.unt.edu/ark:/67531/metadc830245/

    There’s so many papers on this circa 2010 and yet in South Australia we managed to drive off the road, seemingly asleep at the wheel.

    1. Allen Eltor Avatar
      Allen Eltor

      It’s pure KWACK-0-DyE-namicks.

  7. Ian Porter Avatar
    Ian Porter

    Quote:
    “If frequency falls the compressors slow down reducing compression ratio and thus power so even more so more of the governor response is needed just to compensate for reduced air flow”. Unquote

    This is only true in single shaft gas turbines – where the compressor and turbines are connected. In two-shaft machines this is not the case as the compressor runs at within a constant speed range capable of delivering full compressor output. There are efficiency considerations however.

  8. Allen Eltor Avatar
    Allen Eltor

    What happened was the WIND system failed and there wasn’t enough repair in all South Australia to make up for the devastating waste of resources the people of Southern Australia have had to put up with: THEFT of their MONIES to give it to THIEVES who sold them WORTHLESS SCHEMES for MAGIC power from WORTHLESS turbines.

    Those turbines aren’t even designed appropriately for wind power on the planet. They’re designed as outsized mini-turbines and those aren’t efficient.

    Efficiency with wind is provision of some kind of cliff, ducting and trapping the wind that comes over it.

    It’s theft pure and simple by thieves just like the ones who have the West’s education systems teaching children there is such thing as putting insulation between a rock and fire, making more firelight leak out of the rock,
    while making less firelight get to it.

    That’s called refractive loss to space when 20% of total sunlight is blocked by green house gases,

    and losses are cooling.

    Green house gases COOL the planet.
    They cool it through reduction of total energy striking the planet.

    When refraction causes losses to space
    that is called less light arriving at the rock
    than when full light was arriving at the rock.

    Surface energy density reduction through refraction loss is cooling.

    It’s a scam. They’re teaching your children that less sunlight landing on a thermal sensor makes the sensor depict more sunlight leaking back out of the rock the sensor is affixed to.

    The entire fake warming scam is to steal you all blind.

    Al Gore flies around on a jet he bought with YOUR children’s heating money.

    You’d better wise up people – just like it was a scam when the American government sent thieves prowling the entire earth swearing that pot is like heroin

    it’s a criminal act for educators to teach your children there is insulation you can put between a rock and a fire
    that refracts firelight away from the rock
    so less firelight reaches it
    making more firelight come out of the rock
    it’s making less firelight reach.

    Don’t be like the socialist sheeple who believe anybody who says ”I are gubmunt man i wood nevur lye two yew awl!”

    Check their bullshit stories.
    Demand accountability of your government employees
    or they’re going to be shooting you and your children down in the street

    the way they shoot those black and mexican people, those teenagers down, so they can ”save them from addiction to the mariheroinajuana.

    You’ve all been CONNED by GOVERNMENT EMPLOYEES.

    And just like they told your grand daddy that pot is heroin

    and just like they told your daddy that ”thim fridjurants dun burnt up awl thuh Oh!Zone over Ant Art iCKa,”

    now theyre telling you that ”magical gais is making the sky git hot whin yew yewz fire.”

    Teaching your kids that – when you put insulation between a fire and a rock with a thermal sensor fixed to it,

    less light reaching that rock,
    is gonna make that sensor show
    more light leaving that rock.

    Bullshit.

    Which is why people mock those magic gassers TO their FACES.

Get up to 3 quotes from pre-vetted solar (and battery) installers.